VORANT. Threat Intelligence Research Create a free account

Rockwell Logix Controllers Vulnerable to DoS Flaw

Published Vorant ratingroutine vulnerability Manufacturing

Vorant's rating weighs the evidence in the report: confirmed exploitation, victims claimed, CVSS and EPSS, and how many sources agree. It rates the report, not your assets.

A CIP message input validation flaw in Rockwell Automation Logix controllers can trigger a fault requiring manual power cycling to recover.

Sourcecisa.gov — open the original

What to check

Applies to
The 1 CVE named below. Whether you run an affected version is not assessed: check the versions the source lists.
Exploitation
No exploitation in the wild and no public exploit is recorded for the CVEs named.

CISA and Rockwell Automation disclosed a denial-of-service vulnerability (CVE-2026-9637) affecting multiple Logix Platform product lines, including ControlLogix 5580, CompactLogix 5380, GuardLogix 5580, and Compact GuardLogix 5380 across a range of firmware versions. The flaw stems from improper validation of input length during CIP (Common Industrial Protocol) message processing, which can result in a major nonrecoverable fault (MNRF) that halts controller operation and requires a physical power cycle to restore functionality. This affects critical manufacturing environments worldwide where these Rockwell controllers are deployed.

Rockwell has released corrected firmware versions (V37.011, 34.015, 35.014, and 36.013) addressing the issue, and recommends affected customers upgrade. For those unable to patch immediately, standard ICS security best practices are advised, including minimizing network exposure of control system devices, isolating control networks behind firewalls, and using secure remote access methods such as VPNs. CISA notes there is no known public exploitation of this vulnerability at this time, and it appears to be a defect discovered through vendor testing or coordinated disclosure rather than active attacker activity.

The vulnerability is classified under CWE-119 (Improper Restriction of Operations within the Bounds of a Memory Buffer) and could disrupt industrial operations if a malicious or malformed CIP message is sent to an affected controller, causing downtime until manual intervention. Given the safety and availability implications for manufacturing control systems, timely patching is recommended even absent evidence of in-the-wild exploitation.

Mentioned in this report

Vulnerabilities CVE-2026-9637

Source reporting: https://www.cisa.gov/news-events/ics-advisories/icsa-26-244-03

Free public brief. Slack alerts on the vendors you run come with the paid plans, and a new account gets three days of them, no card.

What this brief leaves out

This page is the free tier: the write-up, the severity, the names. In the app the same report carries live profiles of the CVEs it names. The paid plans add the security research and news reporting the free tier leaves out.

It sits in a corpus of 16,436 reports from 149 sources, 661 of them written in the last seven days, and it grows through the day.

A new account starts with three days of all of it, no card, then keeps the government and CERT reporting free. Slack alerts are a paid-plan feature: name the vendors you run and Slack hears about the reports that touch them, not the rest of the week's. Nothing is charged unless you subscribe.

Create a free account   What it costs